BrazeJobs

R-448A PT Chart

Saturation pressure for R-448A from -40°F to 150°F, with liquid (bubble) and vapor (dew) columns. Look up a pressure or temperature, switch to metric, and check typical operating pressures.

By BrazeJobs Team · Updated

R-448A Lookup

Liquid (Bubble)

89.0 psig

Vapor (Dew)

72.1 psig

Bubble Point

29.8°F

Dew Point

39.9°F

Chart range: -40°F to 150°F. Enter vacuum as a negative pressure. Check R-448A superheat and subcooling

R-448A PT Chart

TempLiquid (Bubble)Vapor (Dew)
-40°F4.9 psig0.0 psig
-35°F7.5 psig2.1 psig
-30°F10.4 psig4.4 psig
-25°F13.5 psig7.0 psig
-20°F17.0 psig9.8 psig
-15°F20.8 psig13.0 psig
-10°F24.9 psig16.4 psig
-5°F29.3 psig20.2 psig
0°F34.2 psig24.3 psig
5°F39.4 psig28.8 psig
10°F45.1 psig33.6 psig
15°F51.2 psig38.9 psig
20°F57.8 psig44.6 psig
25°F64.8 psig50.7 psig
30°F72.3 psig57.3 psig
35°F80.4 psig64.4 psig
40°F89.0 psig72.1 psig
45°F98.2 psig80.3 psig
50°F108.0 psig89.0 psig
55°F118.0 psig98.4 psig
60°F129.0 psig108.0 psig
65°F141.0 psig119.0 psig
70°F154.0 psig130.0 psig
75°F167.0 psig142.0 psig
80°F181.0 psig155.0 psig
85°F195.0 psig169.0 psig
90°F211.0 psig183.0 psig
95°F227.0 psig198.0 psig
100°F244.0 psig214.0 psig
105°F262.0 psig231.0 psig
110°F281.0 psig249.0 psig
115°F300.0 psig268.0 psig
120°F321.0 psig288.0 psig
125°F343.0 psig309.0 psig
130°F365.0 psig331.0 psig
135°F389.0 psig355.0 psig
140°F414.0 psig379.0 psig
145°F440.0 psig405.0 psig
150°F467.0 psig433.0 psig

About R-448A

R-448A is a non-flammable HFC/HFO blend for low- and medium-temperature commercial refrigeration. It replaces R-404A in new supermarket systems and retrofits, at about a third of R-404A’s GWP.

It is a zeotropic blend with significant glide, so the chart gives liquid (bubble) and vapor (dew) columns. Superheat uses the dew column, subcooling the bubble column.

  • Supermarket rack systems and display cases
  • Walk-in coolers and freezers, new and retrofit
  • Retrofit of R-404A and R-22 refrigeration

R-448A Properties

Key facts for identifying R-448A and choosing tools, oil and replacements.

Boiling point and critical temperature: Hudson Technologies. GWP: IPCC AR4 values, the basis of EPA’s AIM Act rules. Safety class: ASHRAE Standard 34.
PropertyValue
TypeHFC/HFO blend
CompositionR-32 26%, R-125 26%, R-134a 21%, R-1234yf 20%, R-1234ze(E) 7% by weight
ASHRAE safety classA1
GWP (IPCC AR4)1,387
Boiling point at 1 atm-50.7°F
Critical temperature182.6°F
OilPOE (polyolester)
Trade namesSolstice N40
ReplacesR-404A, R-22
Replaced byNone

Typical R-448A Operating Pressures

Suction pressure is the vapor (dew) pressure at the evaporator temperature; head pressure is the liquid (bubble) pressure at the condensing temperature. The temperatures are common design points, not charging targets.

Calculated from the chart on this page. Real pressures move with load, airflow, ambient temperature and charge.
ConditionEvaporatorSuctionCondensingHead
Walk-in cooler (medium temp)20°F44.6 psig110°F281.0 psig
Walk-in freezer (low temp)-20°F9.8 psig110°F281.0 psig

How to Read the R-448A PT Chart

The chart covers -40°F to 150°F. Pressures are gauge pressure (psig), the number your manifold shows; switch to °C and kPa above if you work in metric.

R-448A is a zeotropic blend, so it boils over a range of temperatures instead of at one point. That range is the glide. The liquid (bubble) column gives the pressure where the first bubble forms; the vapor (dew) column gives the pressure where the last drop of liquid boils off.

At 20°F, the bubble pressure is 57.8 psig and the dew pressure is 44.6 psig. Read the other way, at 44.6 psig the glide is about 10.4°F.

Use the vapor (dew) column for superheat on the suction line and the liquid (bubble) column for subcooling on the liquid line. Mixing them up shifts the answer by the glide.

Superheat and Subcooling Formulas

The PT chart turns a gauge pressure into a saturation temperature. Compare that with a line temperature to get superheat or subcooling.

Superheat

SH = Tsuction − Tdew

Subcooling

SC = Tbubble − Tliquid

Vacuum

inHg = −psig × 2.036

Metric

°C = (°F − 32) × 5/9, kPa = psig × 6.895

Tsuction
Suction line temperature near the outdoor unit or compressor, °F
Tliquid
Liquid line temperature leaving the condenser, °F
Tdew
Dew point at suction pressure (vapor column), °F
Tbubble
Bubble point at liquid pressure (liquid column), °F

Gauge pressure (psig) is pressure above atmospheric. Below 0 psig, the chart shows vacuum in inches of mercury.

Worked Example: R-448A Superheat and Subcooling

Walk-in cooler (medium temp): an R-448A system reads 44.6 psig suction with a 30°F suction line, and 281.0 psig on the liquid line with a 100°F liquid line.

  1. Dew point at 44.6 psig: 20.0°F.
  2. Superheat: 30°F − 20.0°F = 10.0°F.
  3. Bubble point at 281.0 psig: 110.0°F.
  4. Subcooling: 110.0°F − 100°F = 10.0°F.

Result: 10.0°F superheat and 10.0°F subcooling. Compare them with the manufacturer’s targets before adding or recovering refrigerant.

Is R-448A Being Phased Out?

R-448A is a main retrofit and new-system replacement for R-404A. For some new commercial refrigeration categories, EPA’s Technology Transitions rule sets GWP limits below R-448A’s, so check the rule for the system type before specifying it.

It uses the same POE oil as R-404A, which keeps retrofits simpler, but its glide means expansion valves and controls need resetting.

R-448A Field Tips

Practical points for working on R-448A systems, from the sources below.

  1. 1

    Read superheat off the dew column

    R-448A has several degrees of glide. Using the bubble column for superheat makes it look several degrees low and leads to overfeeding the evaporator.

  2. 2

    Reset controls after a retrofit

    Low pressure cut-outs and defrost terminations set for R-404A see different pressures with R-448A. Recalculate them from the chart for the same box temperature.

  3. 3

    Charge as liquid

    Five components separate if charged as vapor. Take liquid from the cylinder and meter it into the suction side through the manifold.

Sources: Honeywell: Solstice N40 (R-448A), ACHR News: Charging refrigeration systems with blended refrigerants, HVAC School: Glide, blends and why you can’t mix refrigerants