Pipe Volume Calculator
Add up the water in one or more runs of copper, PEX or PVC pipe, using the real inside diameter for each type and size. Or enter a flow in GPM to see the velocity and friction loss in every size.
By BrazeJobs Team · Updated
The Pipe
Run 1
Volume
Run 1: 3/4 in, ID 0.785 in
1.26 gal (2.51 per 100 ft)
How to Calculate Pipe Volume
A pipe holds a cylinder of water: the area of the bore times the length. The only hard part is the diameter. The nominal size printed on the pipe is a name, not a measurement, and the inside diameter of a 3/4 inch pipe changes with the material and wall thickness.
Plumbers need pipe volume for hot water wait times, for filling and treating hydronic systems with glycol, for sizing expansion tanks, for flushing and disinfecting new lines, and for estimating the weight of full pipe on hangers.
Nominal Size vs. Inside Diameter
Copper water tube (ASTM B88) and PEX (ASTM F876) use copper tube size: the outside diameter is always 1/8 inch larger than the nominal size. Type K, L and M copper share the same outside diameter and differ only in wall thickness, so Type M has the largest bore. PEX has a much thicker wall, so its bore is smaller than copper of the same nominal size.
PVC (ASTM D1785) uses iron pipe size, with a larger outside diameter than copper. Schedule 80 has a thicker wall and smaller bore than Schedule 40.
- 3/4 inch Type K copper: 0.745 in inside diameter.
- 3/4 inch Type L copper: 0.785 in.
- 3/4 inch Type M copper: 0.811 in.
- 3/4 inch PEX: 0.681 in.
- 3/4 inch PVC Schedule 40: 0.824 in. Schedule 80: 0.742 in.
Pipe Volume, Velocity and Friction Formulas
With d as the inside diameter in inches, a gallon is 231 cubic inches, so each foot of pipe holds 12 × π/4 × d² ÷ 231 gallons. Velocity follows from the same area. Friction loss uses the Hazen-Williams equation for water at ordinary temperatures.
- d
- Inside diameter in inches
- L
- Length of pipe in feet
- V
- Velocity in feet per second
- C
- Hazen-Williams roughness coefficient (higher is smoother)
- R
- Hydraulic radius in feet, d ÷ 48 for a full round pipe
- S
- Friction loss in feet of head per foot of pipe
Copper and PEX inside diameters use the nominal wall; PVC uses the minimum wall in ASTM D1785. Real pipe varies slightly within the standard’s tolerances, so published volumes can differ by a few percent.
Worked Example: Hot Water Wait Time
A bathroom sink is fed by 25 ft of 3/4 inch Type M copper and 30 ft of 1/2 inch Type M copper from the water heater. The faucet runs at 2 GPM.
- 3/4 inch Type M: 0.811 in ID, 0.0268 gal/ft × 25 ft = 0.671 gal.
- 1/2 inch Type M: 0.569 in ID, 0.0132 gal/ft × 30 ft = 0.396 gal.
- Total in the pipe: 1.067 gal. At 2 GPM, that is 32 seconds just to push the cold water out.
Worked Example: Velocity in a 6 GPM Cold Branch
A 6 GPM cold water branch in Type L copper, C = 140, with the CDA cold water limit of 8 ft/s.
- 1/2 inch (0.545 in ID): 0.4085 × 6 ÷ 0.545² = 8.3 ft/s, over the limit, and 25.5 psi of friction per 100 ft.
- 3/4 inch (0.785 in ID): 4.0 ft/s and 4.31 psi per 100 ft.
- 1 inch (1.025 in ID): 2.3 ft/s and 1.18 psi per 100 ft.
Worked Example: Glycol for a Hydronic System
A small hydronic loop has 150 ft of 3/4 inch PEX and 40 ft of 1 inch Type L copper. The boiler lists 2 gallons of water content. The installer wants a 40% propylene glycol mix.
- PEX: 0.681 in ID, 150 ft holds 2.84 gal.
- Copper: 1.025 in ID, 40 ft holds 1.71 gal.
- System: 2.84 + 1.71 + 2 = 6.55 gal.
- Glycol at 40%: 6.55 × 0.40 = 2.62 gal of concentrate.
Gallons per 100 Feet of Pipe
Water held by 100 feet of each pipe type and size, calculated from the inside diameter. A dash means the size is not made in that type.
| Size | Copper K | Copper L | Copper M | PEX | PVC Sch 40 | PVC Sch 80 |
|---|---|---|---|---|---|---|
| 3/8" | 0.66 | 0.75 | 0.83 | 0.53 | - | - |
| 1/2" | 1.13 | 1.21 | 1.32 | 0.96 | 1.58 | 1.22 |
| 5/8" | 1.73 | 1.81 | - | 1.39 | - | - |
| 3/4" | 2.26 | 2.51 | 2.68 | 1.89 | 2.77 | 2.25 |
| 1" | 4.04 | 4.29 | 4.54 | 3.12 | 4.49 | 3.74 |
| 1-1/4" | 6.32 | 6.53 | 6.80 | 4.66 | 7.77 | 6.66 |
| 1-1/2" | 8.95 | 9.24 | 9.51 | 6.51 | 10.58 | 9.18 |
| 2" | 15.66 | 16.08 | 16.47 | 11.15 | 17.43 | 15.34 |
| 2-1/2" | 24.19 | 24.79 | 25.40 | - | 24.87 | 22.02 |
| 3" | 34.48 | 35.39 | 36.26 | - | 38.40 | 34.31 |
| 4" | 60.70 | 61.96 | 63.18 | - | 66.13 | 59.72 |
Maximum GPM in Type L Copper by Velocity Limit
The Copper Development Association recommends 5 to 8 ft/s for cold water, 4 to 5 ft/s for hot water under 140°F, and 2 to 3 ft/s above 140°F. This table uses the top of each range.
| Size | Cold, 8 ft/s | Hot under 140°F, 5 ft/s | Hot over 140°F, 3 ft/s |
|---|---|---|---|
| 1/2" | 5.8 | 3.6 | 2.2 |
| 3/4" | 12.1 | 7.5 | 4.5 |
| 1" | 20.6 | 12.9 | 7.7 |
| 1-1/4" | 31.3 | 19.6 | 11.8 |
| 1-1/2" | 44.4 | 27.7 | 16.6 |
| 2" | 77.2 | 48.2 | 28.9 |
Field Tips
Practical advice from plumbers on the HeatingHelp forum and from Green Building Advisor, Contractor magazine and the Copper Development Association.
Sources: Green Building Advisor: Why your hot water takes so long, Contractor: Ruined by recirc, HeatingHelp: Velocity, Caleffi: Copper velocity limits from the Copper Development Association, R.L. Deppmann: Expansion and compression tanks