Superheat and Subcooling Calculator
Enter your suction and liquid pressures and line temperatures to get superheat and subcooling for R-410A, R-454B, R-32 or R-22. For piston systems, add the indoor wet bulb and outdoor temperature to check the charge against a target superheat.
By BrazeJobs Team · Updated
Gauge Readings
For a fixed orifice (piston) system, add the indoor wet bulb at the return and the outdoor dry bulb at the condenser to get a target superheat.
Superheat
Fixed Orifice Target
8.0°F
Charge Check
Within ±5°F of target.
Subcooling
On a TXV or EEV system, compare this with the target subcooling on the outdoor unit’s data plate or in the installation manual.
What Superheat and Subcooling Tell You
Refrigerant boils in the evaporator and condenses in the condenser at a temperature set by its pressure: the saturation temperature on a pressure-temperature (PT) chart. Superheat and subcooling measure how far the refrigerant is from that saturation point where it leaves each coil.
Superheat is how much warmer the suction line is than the refrigerant’s boiling point at suction pressure. It shows how much of the evaporator is doing work and protects the compressor: zero superheat means liquid may be reaching it. Subcooling is how much cooler the liquid line is than the condensing temperature. It shows that a solid column of liquid is leaving the condenser and feeding the metering device.
Which number you charge by depends on the metering device. Fixed orifice (piston) systems are charged by superheat against a target that changes with indoor humidity and outdoor temperature. TXV and EEV systems hold their own superheat, so they are charged by subcooling against the manufacturer’s target.
Dew Point, Bubble Point and Glide
R-22 and R-32 are single refrigerants: they boil and condense at one temperature for each pressure. R-410A is a near-azeotropic blend with almost no glide. R-454B (R-32 and R-1234yf) has a small glide: at the same pressure, it starts boiling (bubble point) about 2 to 3°F below where it finishes (dew point).
For blends, use the dew point (saturated vapor) for superheat and the bubble point (saturated liquid) for subcooling. This calculator does that automatically. Using the wrong column on R-454B throws the reading off by the full glide.
Superheat and Subcooling Formulas
Saturation temperatures come from the refrigerant’s PT chart at the measured gauge pressure. Line temperatures come from a pipe clamp on the suction line and the liquid line.
- SH
- Superheat in °F
- SC
- Subcooling in °F
- WB
- Indoor wet bulb at the return, °F
- DB
- Outdoor dry bulb at the condenser, °F
The target formula approximates manufacturer charging charts and usually lands within a degree or two of them. Charge to within about ±5°F of the target, and use the manufacturer’s chart when the unit has one. Targets below 5°F are too low to charge to.
Worked Example: R-410A Piston System
An R-410A system with a fixed orifice. Suction pressure is 118.4 psig and the suction line is 58°F. Indoor wet bulb is 64°F and it is 96°F outside.
- Dew point at 118.4 psig: 40.0°F.
- Superheat: 58 − 40.0 = 18.0°F.
- Target: (3 × 64 − 80 − 96) ÷ 2 = 8°F, so the acceptable range is 3 to 13°F.
Worked Example: R-454B TXV Subcooling
An R-454B system with a TXV. Liquid pressure is 375 psig and the liquid line is 105°F.
- Bubble point at 375 psig: 115.3°F.
- Subcooling: 115.3 − 105 = 10.3°F.
Worked Example: Reading R-454B on an R-410A Chart
A tech reads 118 psig suction and a 50°F suction line on an R-454B system, but the gauge is still set to R-410A.
- R-410A dew point at 118 psig: 39.8°F, so superheat reads 10.2°F.
- R-454B dew point at 118 psig: 44.8°F, so the real superheat is 5.2°F.
Pressure Temperature Chart (psig)
Saturation pressure in psig. For R-410A and R-454B, the first number is the liquid (bubble) pressure and the second is the vapor (dew) pressure.
| Temp | R-22 | R-410A liquid / vapor | R-32 | R-454B liquid / vapor |
|---|---|---|---|---|
| 20°F | 43.1 | 78.7 / 78.4 | 80.0 | 75.0 / 70.9 |
| 30°F | 55.0 | 97.4 / 97.0 | 99.1 | 92.9 / 88.1 |
| 40°F | 68.6 | 118.8 / 118.4 | 121.0 | 113.3 / 107.7 |
| 50°F | 84.1 | 143.2 / 142.6 | 145.8 | 136.6 / 130.1 |
| 60°F | 101.6 | 170.7 / 170.1 | 174.0 | 162.9 / 155.4 |
| 70°F | 121.4 | 201.8 / 201.1 | 205.8 | 192.5 / 184.0 |
| 80°F | 143.6 | 236.5 / 235.8 | 241.5 | 225.6 / 216.1 |
| 90°F | 168.4 | 275.4 / 274.5 | 281.3 | 262.5 / 251.9 |
| 100°F | 195.9 | 318.6 / 317.6 | 325.7 | 303.6 / 291.6 |
| 105°F | 210.8 | 341.9 / 340.9 | 349.6 | 325.7 / 313.6 |
| 110°F | 226.4 | 366.4 / 365.4 | 374.9 | 348.9 / 336.4 |
| 115°F | 242.8 | 392.3 / 391.2 | 401.4 | 373.4 / 360.5 |
| 120°F | 260.0 | 419.4 / 418.3 | 429.3 | 399.1 / 385.8 |
Target Superheat Chart for Fixed Orifice Systems
Target superheat in °F by indoor wet bulb (rows) and outdoor dry bulb (columns). A dash means the target is under 5°F, too low to charge to.
| Indoor WB | 70°F | 75°F | 80°F | 85°F | 90°F | 95°F | 100°F | 105°F |
|---|---|---|---|---|---|---|---|---|
| 56°F | 9 | 7 | - | - | - | - | - | - |
| 58°F | 12 | 10 | 7 | - | - | - | - | - |
| 60°F | 15 | 13 | 10 | 8 | 5 | - | - | - |
| 62°F | 18 | 16 | 13 | 11 | 8 | 6 | - | - |
| 64°F | 21 | 19 | 16 | 14 | 11 | 9 | 6 | - |
| 66°F | 24 | 22 | 19 | 17 | 14 | 12 | 9 | 7 |
| 68°F | 27 | 25 | 22 | 20 | 17 | 15 | 12 | 10 |
| 70°F | 30 | 28 | 25 | 23 | 20 | 18 | 15 | 13 |
| 72°F | 33 | 31 | 28 | 26 | 23 | 21 | 18 | 16 |
Field Tips
Practical advice from HVAC School, HVAC Today, ACHR News, AC Service Tech and Ferguson’s technical guides.
Sources: Ferguson: HVAC superheat and subcooling, ACHR News: Charging refrigeration systems with blended refrigerants, HVAC School: Glide, blends and why you can’t mix refrigerants, AC Service Tech: Target superheat, HVAC Today: Airflow gives refrigerant readings their meaning, HVAC School podcast: How to charge an AC