R-22 PT Chart

Saturation pressure for R-22 from -38°F to 150°F. Look up a pressure or temperature, switch to metric, and check typical operating pressures.

By BrazeJobs Team · Updated

R-22 Lookup

Saturation Pressure

68.6 psig

Saturation Temp

40.3°F

Chart range: -38°F to 150°F. Enter vacuum as a negative pressure. Check R-22 superheat and subcooling

R-22 PT Chart

TempPressure
-38°F1.4 psig
-36°F2.2 psig
-34°F3.1 psig
-32°F4.0 psig
-30°F4.9 psig
-28°F5.9 psig
-26°F6.9 psig
-24°F8.0 psig
-22°F9.1 psig
-20°F10.2 psig
-18°F11.4 psig
-16°F12.6 psig
-14°F13.9 psig
-12°F15.2 psig
-10°F16.5 psig
-8°F17.9 psig
-6°F19.4 psig
-4°F20.9 psig
-2°F22.4 psig
0°F24.0 psig
2°F25.7 psig
4°F27.4 psig
6°F29.2 psig
8°F31.0 psig
10°F32.8 psig
12°F34.8 psig
14°F36.8 psig
16°F38.8 psig
18°F40.9 psig
20°F43.1 psig
22°F45.3 psig
24°F47.6 psig
26°F50.0 psig
28°F52.4 psig
30°F55.0 psig
32°F57.5 psig
34°F60.2 psig
36°F62.9 psig
38°F65.7 psig
40°F68.6 psig
42°F71.5 psig
44°F74.5 psig
46°F77.6 psig
48°F80.8 psig
50°F84.1 psig
52°F87.4 psig
54°F90.8 psig
56°F94.4 psig
58°F98.0 psig
60°F101.6 psig
62°F105.4 psig
64°F109.3 psig
66°F113.2 psig
68°F117.3 psig
70°F121.4 psig
72°F125.7 psig
74°F130.0 psig
76°F134.5 psig
78°F139.0 psig
80°F143.6 psig
82°F148.4 psig
84°F153.2 psig
86°F158.2 psig
88°F163.2 psig
90°F168.4 psig
92°F173.7 psig
94°F179.1 psig
96°F184.6 psig
98°F190.2 psig
100°F195.9 psig
105°F210.8 psig
110°F226.4 psig
115°F242.8 psig
120°F260.0 psig
125°F278.0 psig
130°F296.9 psig
135°F316.7 psig
140°F337.4 psig
145°F359.0 psig
150°F381.7 psig

About R-22

R-22 is a single-component HCFC refrigerant that was the standard in US residential and light commercial air conditioning and heat pumps for decades. Because it contains chlorine, it depletes ozone, which is why it was phased out under the Clean Air Act.

Plenty of R-22 systems are still running, so techs still meet it on service calls. A single-component refrigerant has no glide: liquid and vapor share one saturation pressure at each temperature, so the chart below has one pressure column.

  • Residential split AC and heat pumps built before 2010
  • Packaged rooftop units and light commercial AC
  • Older commercial refrigeration and process cooling

R-22 Properties

Key facts for identifying R-22 and choosing tools, oil and replacements.

Boiling point and critical temperature: Hudson Technologies. GWP: IPCC AR4 values, the basis of EPA’s AIM Act rules. Safety class: ASHRAE Standard 34.
PropertyValue
TypeHCFC
Composition100% chlorodifluoromethane
ASHRAE safety classA1
GWP (IPCC AR4)1,810
Boiling point at 1 atm-41.5°F
Critical temperature205.1°F
OilMineral oil or alkylbenzene
Trade namesFreon 22, Genetron 22
ReplacesNone
Replaced byR-410A, R-407C, R-422B

Typical R-22 Operating Pressures

Suction pressure is the vapor (dew) pressure at the evaporator temperature; head pressure is the liquid (bubble) pressure at the condensing temperature. The temperatures are common design points, not charging targets.

Calculated from the chart on this page. Real pressures move with load, airflow, ambient temperature and charge.
ConditionEvaporatorSuctionCondensingHead
AC cooling, 95°F outdoor40°F68.6 psig115°F242.8 psig

How to Read the R-22 PT Chart

The chart covers -38°F to 150°F. Pressures are gauge pressure (psig), the number your manifold shows; switch to °C and kPa above if you work in metric.

The chart has one pressure column because liquid and vapor share the same saturation pressure at each temperature. Use the same column for superheat (suction side) and subcooling (liquid side).

To read it, find the pressure on your gauge and read across to the saturation temperature, or start from a temperature and read the pressure. The lookup above interpolates between rows for you.

Superheat and Subcooling Formulas

The PT chart turns a gauge pressure into a saturation temperature. Compare that with a line temperature to get superheat or subcooling.

Superheat

SH = Tsuction − Tsat

Subcooling

SC = Tsat − Tliquid

Vacuum

inHg = −psig × 2.036

Metric

°C = (°F − 32) × 5/9, kPa = psig × 6.895

Tsuction
Suction line temperature near the outdoor unit or compressor, °F
Tliquid
Liquid line temperature leaving the condenser, °F
Tsat
Saturation temperature at the gauge pressure, °F

Gauge pressure (psig) is pressure above atmospheric. Below 0 psig, the chart shows vacuum in inches of mercury.

Worked Example: R-22 Superheat and Subcooling

AC cooling, 95°F outdoor: an R-22 system reads 68.6 psig suction with a 50°F suction line, and 242.8 psig on the liquid line with a 105°F liquid line.

  1. Saturation temperature at 68.6 psig: 40.0°F.
  2. Superheat: 50°F − 40.0°F = 10.0°F.
  3. Saturation temperature at 242.8 psig: 115.0°F.
  4. Subcooling: 115.0°F − 105°F = 10.0°F.

Result: 10.0°F superheat and 10.0°F subcooling. Compare them with the manufacturer’s targets before adding or recovering refrigerant.

Is R-22 Being Phased Out?

R-22 is phased out. US production and import ended on January 1, 2020. Owners can keep running existing systems, and service relies on recovered, reclaimed and stockpiled R-22, so prices stay high.

New equipment uses R-410A or, since 2025, low-GWP refrigerants such as R-454B and R-32. When an R-22 system needs a major repair, the usual choices are replacing it or retrofitting it to an HFC blend such as R-407C or R-422B.

R-22 Field Tips

Practical points for working on R-22 systems, from the sources below.

  1. 1

    Recover, don’t top off blindly

    Every pound of R-22 is reclaimed or stockpiled supply. Find and fix the leak before adding refrigerant; topping off a leaking system costs the customer more each season.

  2. 2

    Weigh the retrofit against replacement

    A retrofit adds labor for oil changes, filter driers and TXV adjustment, and the HFC blends lose some capacity. On an old system with a failed compressor or coil, replacement usually makes more sense.

  3. 3

    Label the system after a retrofit

    Tag the unit with the new refrigerant and oil so the next tech does not add R-22 to an R-422B or R-407C system. Mixed refrigerants cannot be reclaimed and must be destroyed.

Sources: EPA: Residential air conditioning and the phaseout of HCFC-22, EPA: Choosing the right R-22 retrofit, ACHR News: R-22 retrofit round-up