CFM Calculator
Work out airflow in cubic feet per minute four ways: from a room’s volume and air changes per hour, from a heating or cooling load, from a duct’s size and air velocity, or from the ventilation rates in ASHRAE 62.2 and the IRC.
By BrazeJobs Team · Updated
Inputs
Airflow
Which CFM Method to Use
CFM, cubic feet per minute, is the volume of air a fan, duct or register moves. There is no single CFM formula because the right answer depends on why you need the air.
- Air changes per hour: for exhaust, fresh air, workshops, server closets and other spaces where you want to replace the room’s air a set number of times per hour.
- BTU load and temperature difference: for heating and cooling supply air. This is how much air it takes to carry a load at a given supply temperature, and it is how room CFM is set in a Manual J and Manual D design.
- Duct size and velocity: for checking how much air an existing duct carries when you measure the velocity, or what a duct can carry at a design velocity.
- Ventilation code: for the continuous fresh air a house needs (ASHRAE 62.2 or the IRC) and the minimum bathroom and kitchen exhaust.
Air Changes per Hour vs. Load-Based Airflow
Many CFM calculators give a target ACH for each room, like 5 to 6 for a bedroom or 7 to 9 for a kitchen, and multiply by the room volume. Those targets are rules of thumb. No residential code sets supply airflow by air changes per hour.
For heating and cooling, a room needs the airflow that carries its share of the load. A south-facing bedroom with big windows needs more air than an interior bedroom of the same size. Use ACH for exhaust and ventilation targets you have been given, and the load method for supply air.
On a whole system, the cooling airflow usually lands near 400 CFM per ton of capacity. Humid climates often run closer to 350 for better moisture removal, and dry climates 450 or more.
CFM Formulas
All four methods are simple ratios. The 1.08 constant is the sensible heat of standard air at sea level: 60 minutes × 0.075 lb per cubic foot × 0.24 BTU per pound per °F.
- L, W, H
- Room length, width and ceiling height in feet
- ACH
- Air changes per hour
- ΔT
- Temperature difference between supply and room (or return) air, °F
- A
- Duct cross-section in square feet (rectangular: W × H ÷ 144)
- V
- Average air velocity in feet per minute
Use only the sensible part of a cooling load in the BTU formula. Total capacity includes the latent load (moisture), which does not change the air temperature.
Worked Example: Bedroom at 6 Air Changes
A 12 by 15 ft bedroom with 8 ft ceilings, at a target of 6 air changes per hour.
- Volume: 12 × 15 × 8 = 1,440 cubic feet.
- Airflow: 1,440 × 6 ÷ 60 = 144 CFM.
Worked Example: Airflow for a 3-Ton Air Conditioner
A 3-ton (36,000 BTU/h) system with a sensible capacity of 27,000 BTU/h and a 20°F difference between return and supply air.
- Airflow: 27,000 ÷ (1.08 × 20) = 1,250 CFM.
- Per ton: 1,250 ÷ 3 = 417 CFM per ton, close to the usual 400.
Worked Example: Furnace Airflow From Temperature Rise
A 60,000 BTU/h input furnace at 96% AFUE (about 57,600 BTU/h output) with a measured temperature rise of 50°F.
- Airflow: 57,600 ÷ (1.08 × 50) = 1,067 CFM.
Worked Example: Whole-House Ventilation
A 2,000 sq ft house with 3 bedrooms.
- ASHRAE 62.2: 0.03 × 2,000 + 7.5 × (3 + 1) = 60 + 30 = 90 CFM.
- IRC: 0.01 × 2,000 + 7.5 × (3 + 1) = 20 + 30 = 50 CFM.
CFM per Ton Chart
Total system airflow for common air conditioner and heat pump sizes at three airflow targets.
| System size | Humid (350 CFM/ton) | Standard (400 CFM/ton) | Dry (450 CFM/ton) |
|---|---|---|---|
| 1.5 tons (18,000 BTU/h) | 525 | 600 | 675 |
| 2 tons (24,000 BTU/h) | 700 | 800 | 900 |
| 2.5 tons (30,000 BTU/h) | 875 | 1,000 | 1,125 |
| 3 tons (36,000 BTU/h) | 1,050 | 1,200 | 1,350 |
| 3.5 tons (42,000 BTU/h) | 1,225 | 1,400 | 1,575 |
| 4 tons (48,000 BTU/h) | 1,400 | 1,600 | 1,800 |
| 5 tons (60,000 BTU/h) | 1,750 | 2,000 | 2,250 |
Round Duct CFM by Velocity
Airflow a round duct carries at three common design velocities. Size for friction too: a small duct can reach the velocity long before it reaches the CFM.
| Diameter | Area (sq ft) | CFM at 600 fpm | CFM at 700 fpm | CFM at 900 fpm |
|---|---|---|---|---|
| 4" | 0.087 | 52 | 61 | 79 |
| 5" | 0.136 | 82 | 95 | 123 |
| 6" | 0.196 | 118 | 137 | 177 |
| 7" | 0.267 | 160 | 187 | 241 |
| 8" | 0.349 | 209 | 244 | 314 |
| 9" | 0.442 | 265 | 309 | 398 |
| 10" | 0.545 | 327 | 382 | 491 |
| 12" | 0.785 | 471 | 550 | 707 |
| 14" | 1.069 | 641 | 748 | 962 |
| 16" | 1.396 | 838 | 977 | 1,257 |
| 18" | 1.767 | 1,060 | 1,237 | 1,590 |
| 20" | 2.182 | 1,309 | 1,527 | 1,963 |
Field Tips
Practical advice from Green Building Advisor, Greenheck, Contracting Business and HVAC School, checked against the code.
Sources: Greenheck: Specifying ceiling exhaust fans to meet code, Green Building Advisor: Makeup air for kitchen exhaust, Contracting Business: How to take an accurate supply register airflow reading, Green Building Advisor: Simple methods for measuring air flow, HVAC School: Furnace air temperature rise