Manual J Heating Load Calculator
Enter each room’s floor area, outside wall and glass, pick your design temperature and construction, and get a room-by-room heating load in BTU/h with each room’s share of the system airflow.
By BrazeJobs Team · Updated
Design Conditions
Indoor design temperature is 70°F. Edit any U-value to match your actual walls, windows and attic, and use a blower door result for air changes if you have one.
Rooms
Heating Load
| Room | BTU/h | Share | CFM |
|---|---|---|---|
| Living room | 6,810 | 38% | 301 |
| Kitchen | 3,204 | 18% | 142 |
| Bedroom 1 | 4,443 | 25% | 197 |
| Bedroom 2 | 3,632 | 20% | 161 |
Walls
3,647 BTU/h
Windows
4,420 BTU/h
Ceilings
1,809 BTU/h
Slab edge
4,865 BTU/h
Air leakage
3,349 BTU/h
Heating only. Duct losses in unconditioned space, basements, crawlspaces and cooling loads are not included. Room CFM splits the system airflow by each room’s share of the load.
What a Manual J Load Calculation Does
ACCA Manual J is the industry standard for calculating how much heat a house loses in winter and gains in summer. It works room by room: each room’s walls, windows, ceiling, floor and air leakage are added up at the local design temperature. The whole-house total sizes the equipment under Manual S, and the room loads set the airflow to each room for duct design under Manual D.
This calculator does the heating side of that process with the same physics: heat flow through each surface is its U-value times its area times the temperature difference, plus the heat needed to warm the outside air that leaks in. It is a Manual J-style calculation, not ACCA-approved software, and it does not calculate cooling loads.
What You Need to Measure
The calculation is only as good as its inputs. For each room you need:
- Floor area, which sets the ceiling area and the room’s air volume.
- The length of wall that faces outside. Interior walls between heated rooms do not lose heat.
- Glass area: windows and glass doors, measured as rough openings.
- What is above (attic or roof versus another heated floor) and below (slab on grade versus heated space).
- For the house: the 99% winter design temperature for your location, the ceiling height, and U-values for walls, windows and ceiling, ideally from the actual products.
Heating Load Formulas
Each room is calculated separately, then added. ΔT is 70°F minus the outdoor design temperature.
- Q
- Heat loss in BTU per hour
- U
- Heat flow per sq ft per °F (1 ÷ R-value of the whole assembly)
- F
- Slab edge heat loss per foot of perimeter per °F
- ACH
- Natural air changes per hour at design conditions
Heat loss through a wall uses the whole-assembly U-value, which includes the studs, not just the insulation’s R-value.
Worked Example: Corner Bedroom in Chicago
A 12 by 14 ft corner bedroom (168 sq ft) with 26 ft of outside wall, 8 ft ceilings, 30 sq ft of windows, an attic above and a slab below. Average construction, Chicago design temperature of 2°F.
- ΔT: 70 − 2 = 68°F. Net wall: 26 × 8 − 30 = 178 sq ft.
- Walls: 0.082 × 178 × 68 = 993 BTU/h. Windows: 0.5 × 30 × 68 = 1,020 BTU/h.
- Ceiling: 0.035 × 168 × 68 = 400 BTU/h. Slab edge: 0.73 × 26 × 68 = 1,291 BTU/h.
- Air leakage: 0.45 ACH × 1,344 cu ft ÷ 60 = 10.08 CFM, and 1.08 × 10.08 × 68 = 740 BTU/h.
Worked Example: Splitting Airflow Between Rooms
The calculator’s starting four-room plan (760 sq ft) in Chicago with average construction, and a blower delivering 800 CFM on heat.
- Room loads: living room 6,810, kitchen 3,204, bedroom 1 4,443 and bedroom 2 3,632 BTU/h.
- Total: 18,089 BTU/h, about 23.8 BTU/h per sq ft.
- Shares: 37.6%, 17.7%, 24.6% and 20.1%, so 301, 142, 197 and 161 CFM.
Worked Example: Getting the Window U-Value Right
The same house, but the windows are double-pane low-e at U-0.30 instead of the U-0.50 default.
- Window loss drops from 4,420 to 2,652 BTU/h.
- Total load drops from 18,089 to 16,321 BTU/h, about 10% less.
Construction Presets
Starting values for each construction choice. Replace them with your actual assembly U-values when you know them.
| Construction | Wall U | Window U | Ceiling U | Slab F | ACH |
|---|---|---|---|---|---|
| Poor (pre-1970s, little insulation) | 0.25 | 1 | 0.08 | 0.73 | 0.9 |
| Average (R-13 walls, R-30 attic) | 0.082 | 0.5 | 0.035 | 0.73 | 0.45 |
| New home (current energy code) | 0.045 | 0.3 | 0.024 | 0.73 | 0.2 |
Field Tips
Advice from ACCA and Energy Vanguard on the Manual J inputs that most often go wrong.
Sources: Energy Vanguard: Got Manual J? Don’t assume it’s correct, ACCA: Making mistakes with Manual J, ACCA Outdoor Design Conditions Guide