R-32 PT Chart

Saturation pressure for R-32 from -38°F to 150°F. Look up a pressure or temperature, switch to metric, and check typical operating pressures.

By BrazeJobs Team · Updated

R-32 Lookup

Saturation Pressure

121.0 psig

Saturation Temp

40.0°F

Chart range: -38°F to 150°F. Enter vacuum as a negative pressure. Check R-32 superheat and subcooling

R-32 PT Chart

TempPressure
-38°F12.4 psig
-36°F13.7 psig
-34°F15.2 psig
-32°F16.6 psig
-30°F18.2 psig
-28°F19.8 psig
-26°F21.4 psig
-24°F23.2 psig
-22°F25.0 psig
-20°F26.8 psig
-18°F28.7 psig
-16°F30.7 psig
-14°F32.8 psig
-12°F34.9 psig
-10°F37.1 psig
-8°F39.4 psig
-6°F41.7 psig
-4°F44.1 psig
-2°F46.7 psig
0°F49.2 psig
2°F51.9 psig
4°F54.7 psig
6°F57.5 psig
8°F60.5 psig
10°F63.5 psig
12°F66.6 psig
14°F69.8 psig
16°F73.1 psig
18°F76.5 psig
20°F80.0 psig
22°F83.6 psig
24°F87.3 psig
26°F91.1 psig
28°F95.1 psig
30°F99.1 psig
32°F103.2 psig
34°F107.5 psig
36°F111.8 psig
38°F116.3 psig
40°F121.0 psig
42°F125.7 psig
44°F130.5 psig
46°F135.5 psig
48°F140.6 psig
50°F145.8 psig
52°F151.2 psig
54°F156.7 psig
56°F162.4 psig
58°F168.1 psig
60°F174.0 psig
62°F180.1 psig
64°F186.3 psig
66°F192.7 psig
68°F199.2 psig
70°F205.8 psig
72°F212.6 psig
74°F219.6 psig
76°F226.7 psig
78°F234.0 psig
80°F241.5 psig
82°F249.1 psig
84°F256.9 psig
86°F264.9 psig
88°F273.0 psig
90°F281.3 psig
92°F289.8 psig
94°F298.5 psig
96°F307.4 psig
98°F316.4 psig
100°F325.7 psig
105°F349.6 psig
110°F374.9 psig
115°F401.4 psig
120°F429.3 psig
125°F458.7 psig
130°F489.5 psig
135°F521.8 psig
140°F555.8 psig
145°F591.4 psig
150°F628.8 psig

About R-32

R-32 is a single-component HFC and half of the R-410A blend. Used on its own, it has about a third of R-410A’s GWP, which puts it under the 700 GWP limit for new US residential AC and heat pumps.

R-32 is classed A2L, mildly flammable. As a single component it has no glide, so the chart has one pressure column. Its pressures run slightly above R-410A, and its discharge temperatures run noticeably hotter.

  • New residential split AC and heat pumps, including Daikin and its Goodman and Amana brands
  • Ductless mini-splits, widely used in Asia and Europe for years
  • Component of R-410A, R-454B, R-407C and R-448A

R-32 Properties

Key facts for identifying R-32 and choosing tools, oil and replacements.

Boiling point and critical temperature: Hudson Technologies. GWP: IPCC AR4 values, the basis of EPA’s AIM Act rules. Safety class: ASHRAE Standard 34.
PropertyValue
TypeHFC
Composition100% difluoromethane
ASHRAE safety classA2L
GWP (IPCC AR4)675
Boiling point at 1 atm-61°F
Critical temperature172.6°F
OilPOE (polyolester)
Trade namesDifluoromethane, HFC-32
ReplacesR-410A
Replaced byNone

Typical R-32 Operating Pressures

Suction pressure is the vapor (dew) pressure at the evaporator temperature; head pressure is the liquid (bubble) pressure at the condensing temperature. The temperatures are common design points, not charging targets.

Calculated from the chart on this page. Real pressures move with load, airflow, ambient temperature and charge.
ConditionEvaporatorSuctionCondensingHead
AC cooling, 95°F outdoor40°F121.0 psig115°F401.4 psig

How to Read the R-32 PT Chart

The chart covers -38°F to 150°F. Pressures are gauge pressure (psig), the number your manifold shows; switch to °C and kPa above if you work in metric.

The chart has one pressure column because liquid and vapor share the same saturation pressure at each temperature. Use the same column for superheat (suction side) and subcooling (liquid side).

To read it, find the pressure on your gauge and read across to the saturation temperature, or start from a temperature and read the pressure. The lookup above interpolates between rows for you.

Superheat and Subcooling Formulas

The PT chart turns a gauge pressure into a saturation temperature. Compare that with a line temperature to get superheat or subcooling.

Superheat

SH = Tsuction − Tsat

Subcooling

SC = Tsat − Tliquid

Vacuum

inHg = −psig × 2.036

Metric

°C = (°F − 32) × 5/9, kPa = psig × 6.895

Tsuction
Suction line temperature near the outdoor unit or compressor, °F
Tliquid
Liquid line temperature leaving the condenser, °F
Tsat
Saturation temperature at the gauge pressure, °F

Gauge pressure (psig) is pressure above atmospheric. Below 0 psig, the chart shows vacuum in inches of mercury.

Worked Example: R-32 Superheat and Subcooling

AC cooling, 95°F outdoor: an R-32 system reads 121.0 psig suction with a 50°F suction line, and 401.4 psig on the liquid line with a 105°F liquid line.

  1. Saturation temperature at 121.0 psig: 40.0°F.
  2. Superheat: 50°F − 40.0°F = 10.0°F.
  3. Saturation temperature at 401.4 psig: 115.0°F.
  4. Subcooling: 115.0°F − 105°F = 10.0°F.

Result: 10.0°F superheat and 10.0°F subcooling. Compare them with the manufacturer’s targets before adding or recovering refrigerant.

Is R-32 Being Phased Out?

R-32 is one of the two main replacements for R-410A in new US residential equipment, alongside R-454B. With a GWP of 675, it meets the 700 limit that took effect for new systems in 2025.

Because it is an A2L refrigerant, R-32 equipment carries extra safety requirements: leak detection and mitigation controls in some systems, A2L-rated recovery machines and vacuum pumps, and storage rules for cylinders.

R-32 Field Tips

Practical points for working on R-32 systems, from the sources below.

  1. 1

    Expect a smaller charge

    R-32 systems hold less refrigerant than an R-410A system of the same size. Charge by the nameplate weight and the manufacturer’s subcooling target; habits from R-410A lead to overcharging.

  2. 2

    Watch discharge temperature

    R-32 discharge temperatures run well above R-410A at the same conditions. A high reading is not automatically a fault, but compare it with the manufacturer’s limit before you call the compressor bad.

  3. 3

    Use A2L-rated equipment

    Recovery machines, vacuum pumps and leak detectors that touch the refrigerant need to be rated for A2L refrigerants. Ventilate the work area and keep ignition sources away from open lines.

Sources: IIR: Study of R-32 for residential air conditioning, Ferguson: A2L refrigerant tool compatibility, Chadwell Supply: A2L refrigerant tools and storage